Sure, but when you stick a UPS in the closet to power your network or security cameras or whatever for a little while if there is a power interruption, you expect:

a) If the power is out too long for your UPS (or you have solar and batteries and they discharge overnight or whatever) that the system will turn back on when the power recovers, and

b) You will not have extra bonus outages just because the UPS is in a bad mood.

 help



I completely agree with B. But alas, people love buying shitty cheap UPSes.

But A is along the lines of the misconception that I'm referring to... There should be no such thing as "the power being out too long for your UPS". A UPS isn't there to give you a little while to ignore the problem, it's there to give you time to address it. Either by switching to another source of power, or to power off the equipment.

Now, the reason that every UPS that supports auto-restart has it as a configurable option, is because you often don't want to do this for many reasons, e.g.:

* a low SOC battery could not guarantee a minimum runtime for safe shutdown during a repeated outage

* a catastrophic failure (because the battery shouldn't be dead) could be an indication of other issues that need to be addressed before power on

* powering on the equipment may require staggering to prevent inrush current overload

The whole use case of "I'm using the UPS to run my equipment during an outage" is kind of an abuse of their purpose. It's commonly done, and I've done it myself. But it's not what they're for.

But also, if you want a UPS that auto-restarts -- they exist -- but you get what you pay for.


Some of these is IMO a bit silly:

> a low SOC battery could not guarantee a minimum runtime for safe shutdown during a repeated outage

A lot of devices are unconditionally safe to shut down. Think network equipment, signs, exit lights, and well designed computers.

> a catastrophic failure (because the battery shouldn't be dead) could be an indication of other issues that need to be addressed before power on

This is such a weird presumption. Power outages happen. Long power outages happen. Fancy management software that triggers a controlled shutdown when the SOC is low might still leave nonzero remaining load. In fact, if you have a load that uses a UPS to trigger a controlled shutdown, it’s almost definitional that a controlled shutdown is not a catastrophe and that the system should turn back on eventually.

All of your points are valid for serious datacenter gear and even for large server closets, but for small systems I think they don’t apply to most users, and I’m talking about smaller UPSes.


> > a low SOC battery could not guarantee a minimum runtime for safe shutdown during a repeated outage

> A lot of devices are unconditionally safe to shut down.

Yeah, but that doesn't mean you want to expose them to brownout conditions when your UPS is depleted. If the power is continuing to flip on and off, it's better to just leave it off if you don't have the battery to prevent even short interruptions. A good UPS can do this automatically for you. A cheap one will just stay off and let you respond to the outage.

> This is such a weird presumption.

It wasn't a presumption I was making for all users -- but an example of why some users might not want auto-restart as a feature. Of course, if you want auto-restart as a feature, you can buy a UPS that has it as a feature and turn it on.

> they don’t apply to most users, and I’m talking about smaller UPSes.

Yeah, I know the situation: Someone has a network closet on a budget with a UPS they've sized to get them a few minutes of runtime. They put a UPS on the BOM because it checks a box. So they buy a low-end UPS that either doesn't have the feature, or it doesn't work right.

The solution is just to buy the right UPS for the thing they were trying to do... and test it.